| K-0353 | Inspect, test, and maintain automatic sprinkler systems. Smoke Deficiencies | 16,500 | 9,765 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. Gas, Vacuum, and Electrical Systems Deficiencies | 11,281 | 7,559 |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. Smoke Deficiencies | 9,125 | 6,470 |
| K-0363 | Install corridor and hallway doors that block smoke. Smoke Deficiencies | 8,831 | 6,055 |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. Smoke Deficiencies | 8,378 | 6,068 |
| K-0712 | Have simulated fire drills held at unexpected times. Miscellaneous Deficiencies | 8,183 | 5,637 |
| K-0920 | Ensure proper usage of power strips and extension cords. Gas, Vacuum, and Electrical Systems Deficiencies | 7,654 | 5,344 |
| K-0324 | Provide properly protected cooking facilities. Smoke Deficiencies | 7,649 | 5,843 |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. Smoke Deficiencies | 5,935 | 4,576 |
| K-0511 | Have properly installed electrical wiring and gas equipment. Services Deficiencies | 5,738 | 4,249 |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. Egress Deficiencies | 5,216 | 4,129 |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. Egress Deficiencies | 5,208 | 4,107 |
| K-0923 | Have proper medical gas storage and administration areas. Gas, Vacuum, and Electrical Systems Deficiencies | 5,178 | 4,257 |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. Smoke Deficiencies | 4,702 | 3,804 |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. Miscellaneous Deficiencies | 4,666 | 3,757 |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. Services Deficiencies | 4,551 | 3,231 |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. Egress Deficiencies | 3,946 | 3,272 |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. Miscellaneous Deficiencies | 3,787 | 3,029 |
| K-0351 | Install an approved automatic sprinkler system. Smoke Deficiencies | 3,768 | 3,141 |
| F-0921 | Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public. Environmental Deficiencies | 3,427 | 2,570 |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. Smoke Deficiencies | 3,126 | 2,586 |
| K-0293 | Have properly located and lighted "Exit" signs. Egress Deficiencies | 3,119 | 2,660 |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. Gas, Vacuum, and Electrical Systems Deficiencies | 2,931 | 2,538 |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. Egress Deficiencies | 2,351 | 1,987 |
| K-0161 | Use approved construction type or materials. Construction Deficiencies | 2,222 | 1,719 |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. Gas, Vacuum, and Electrical Systems Deficiencies | 2,167 | 1,758 |
| F-0908 | Keep all essential equipment working safely. Environmental Deficiencies | 1,934 | 1,660 |
| F-0925 | Make sure there is a pest control program to prevent/deal with mice, insects, or other pests. Environmental Deficiencies | 1,855 | 1,492 |
| F-0919 | Make sure that a working call system is available in each resident's bathroom and bathing area. Environmental Deficiencies | 1,831 | 1,564 |
| K-0711 | Provide a written emergency evacuation plan. Miscellaneous Deficiencies | 1,769 | 1,545 |
| K-0341 | Install a fire alarm system that can be heard throughout the facility. Smoke Deficiencies | 1,669 | 1,546 |
| K-0271 | Have exits that are accessible at all times. Egress Deficiencies | 1,509 | 1,339 |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. Gas, Vacuum, and Electrical Systems Deficiencies | 1,441 | 1,299 |
| K-0781 | Have restrictions on the use of portable space heaters. Miscellaneous Deficiencies | 1,222 | 1,142 |
| K-0311 | Have an enclosure around a vertical opening shaft. Smoke Deficiencies | 1,189 | 937 |
| K-0354 | Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours. Smoke Deficiencies | 1,162 | 1,023 |
| K-0919 | Meet requirements for the use of electrical equipment. Gas, Vacuum, and Electrical Systems Deficiencies | 1,154 | 924 |
| K-0281 | Install proper backup exit lighting. Egress Deficiencies | 1,061 | 949 |
| K-0225 | Have stairways and smokeproof enclosures used as exits that meet safety requirements. Egress Deficiencies | 1,057 | 888 |
| K-0362 | Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke. Smoke Deficiencies | 1,043 | 928 |
| K-0347 | Properly provide smoke detection systems in areas open to corridors. Smoke Deficiencies | 1,028 | 893 |
| K-0346 | Follow proper procedures when the fire alarm was out of service for more than 4 hours. Smoke Deficiencies | 972 | 894 |
| F-0912 | Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms. Environmental Deficiencies | 941 | 393 |
| K-0100 | Meet other general requirements. Construction Deficiencies | 908 | 788 |
| K-0531 | Have elevators that firefighters can control in the event of a fire. Services Deficiencies | 879 | 730 |
| K-0916 | Have a battery powered remote alarm panel in a location accessible by operating personnel. Gas, Vacuum, and Electrical Systems Deficiencies | 815 | 781 |
| K-0912 | Have power receptacles that are properly grounded. Gas, Vacuum, and Electrical Systems Deficiencies | 803 | 733 |
| K-0753 | Have restrictions on the use of highly flammable decorations. Miscellaneous Deficiencies | 737 | 698 |
| K-0325 | Have properly installed hallway dispensers for alcohol-based hand rub. Smoke Deficiencies | 682 | 648 |
| K-0232 | Have corridors or aisles that are unobstructed and are at least 8 feet in width. Egress Deficiencies | 638 | 560 |
| K-0342 | Have a complete alarm system manually initiated and initiated by fire sprinkler system connection. Smoke Deficiencies | 606 | 550 |
| K-0500 | Meet other general requirements that are deficient. Services Deficiencies | 603 | 542 |
| K-0541 | Install properly constructed and protected linen or trash chutes. Services Deficiencies | 599 | 481 |
| K-0926 | Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk. Gas, Vacuum, and Electrical Systems Deficiencies | 548 | 482 |
| F-0909 | Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame. Environmental Deficiencies | 490 | 459 |
| K-0331 | Construct fire resistant interior walls. Smoke Deficiencies | 477 | 452 |
| K-0300 | Meet other general requirements that are deficient. Egress Deficiencies | 461 | 398 |
| K-0131 | Meet requirements for sections of health care facilities separated by fire resistive construction. Construction Deficiencies | 427 | 384 |
| K-0343 | Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire. Smoke Deficiencies | 415 | 397 |
| K-0352 | Properly install and monitor supervisory attachments on automatic sprinkler systems. Smoke Deficiencies | 410 | 395 |
| K-0915 | Have proper power supply for life support equipment. Gas, Vacuum, and Electrical Systems Deficiencies | 396 | 341 |
| K-0929 | Ensure precautions for handling oxygen cylinders and equipment are correctly followed. Gas, Vacuum, and Electrical Systems Deficiencies | 389 | 362 |
| K-0927 | Have proper fire barriers, ventilation and signs for the transfilling of oxygen. Gas, Vacuum, and Electrical Systems Deficiencies | 387 | 351 |
| K-0344 | Have an alternate power supply for its alarm system. Smoke Deficiencies | 358 | 329 |
| K-0133 | Install a two-hour-resistant firewall separation. Construction Deficiencies | 326 | 261 |
| K-0200 | Meet other general requirements. Egress Deficiencies | 307 | 296 |
| F-0926 | Have policies on smoking. Environmental Deficiencies | 289 | 273 |
| K-0901 | Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel. Electrical Deficiencies | 274 | 261 |
| K-0754 | Provide properly sized and located linen or trash receptacles. Miscellaneous Deficiencies | 262 | 237 |
| K-0361 | Ensure that waiting areas, nurse’s stations, gift shops, and cooking facilities, open to the corridor are properly protected. Smoke Deficiencies | 253 | 243 |
| K-0522 | Have an externally vented heating system. Services Deficiencies | 221 | 213 |
| K-0922 | Meet requirements for the use and maintenance of medical gas equipment. Gas, Vacuum, and Electrical Systems Deficiencies | 219 | 196 |
| F-0924 | Put firmly secured handrails on each side of hallways. Environmental Deficiencies | 195 | 190 |
| K-0371 | Have properly sized and located compartments to protect residents from smoke. Smoke Deficiencies | 185 | 170 |
| K-0700 | Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors. Miscellaneous Deficiencies | 185 | 180 |
| K-0111 | Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy. Construction Deficiencies | 172 | 164 |
| K-0226 | Have horizontal exits used in accordance with safety requirements. Egress Deficiencies | 167 | 156 |
| F-0911 | Ensure resident rooms hold no more than 4 residents; for new construction after November 28, 2016, rooms hold no more than 2 residents. Environmental Deficiencies | 161 | 64 |
| F-0914 | Provide bedrooms that don't allow residents to see each other when privacy is needed. Environmental Deficiencies | 161 | 154 |
| F-0923 | Have enough outside ventilation via a window or mechanical ventilation, or both. Environmental Deficiencies | 140 | 133 |
| K-0751 | Have restrictions on the use of flammable curtains. Miscellaneous Deficiencies | 140 | 136 |
| K-0908 | Ensure gas and vacuum systems are inspected and tested as part of a maintenance program. Gas, Vacuum, and Electrical Systems Deficiencies | 127 | 117 |
| K-0132 | Meet requirements for outpatient facilities located next to inpatient facilities separated by fire resistive construction. Construction Deficiencies | 119 | 108 |
| K-0364 | Install properly constructed windows in hallway walls or doors. Smoke Deficiencies | 119 | 118 |
| K-0932 | Meet other general requirements. Smoke Deficiencies | 115 | 112 |
| K-0925 | Ensure that sources of ignition are removed from patients receiving respiratory therapy. Gas, Vacuum, and Electrical Systems Deficiencies | 112 | 107 |
| K-0900 | Meet Health Care Facilities Code mechanical requirements. Miscellaneous Deficiencies | 110 | 106 |
| K-0917 | Ensure electrical receptacles or cover plates have distinctive color or marking. Gas, Vacuum, and Electrical Systems Deficiencies | 106 | 105 |
| K-0241 | Have correct number of accessible exits for each story. Egress Deficiencies | 101 | 56 |
| K-0227 | Have ramps, exits, fire escape ladders, steps, and areas of refuge that meet safety requirements. Egress Deficiencies | 84 | 82 |
| K-0930 | Ensure proper storage of liquid oxygen. Gas, Vacuum, and Electrical Systems Deficiencies | 82 | 77 |
| K-0907 | Ensure medical gas and vacuum systems have documented maintenance programs. Gas, Vacuum, and Electrical Systems Deficiencies | 78 | 73 |
| K-0221 | Provide rooms that can be unlocked from inside without a key. Egress Deficiencies | 75 | 75 |
| K-0252 | Provide at least two remote exits on each floor or fire section of the building. Egress Deficiencies | 75 | 47 |
| F-0917 | Make sure each resident has 1) at least one window to the outside in a room; 2) a room at or above ground level; 3) adequate bedding; 4) furniture that meets the resident's needs; or 5) adequate closet space. Environmental Deficiencies | 64 | 64 |
| F-0920 | Provide at least one room set aside to use as a resident dining room and for activities, that is a good size, with good lighting, air flow and furniture. Environmental Deficiencies | 60 | 59 |
| K-0233 | Install resident room doors of proper design and width. Egress Deficiencies | 58 | 48 |
| K-0771 | Ensure that smoke control systems are tested and documented in accordance with established engineering principles. Miscellaneous Deficiencies | 51 | 49 |
| K-0791 | Ensure that any exit in an area undergoing construction, repair, or improvements shall be inspected daily to ensure its ability to be used instantly in case of emergency. Miscellaneous Deficiencies | 50 | 49 |
| K-0913 | Ensure operating rooms are properly protected and written records are maintained and available for inspection. Gas, Vacuum, and Electrical Systems Deficiencies | 50 | 49 |
| K-0163 | Install noncombustible or limited-combustible interior walls. Construction Deficiencies | 47 | 43 |
| K-0224 | Provide sliding doors free of hazards, operable without special knowledge or effort, and meet weight requirements to set door in motion. Egress Deficiencies | 45 | 44 |
| F-0922 | Have enough backup water supply for essential areas of the nursing home. Environmental Deficiencies | 41 | 41 |
| K-0928 | Ensure equipment listed for use in oxygen-enriched atmospheres are correctly labeled. Gas, Vacuum, and Electrical Systems Deficiencies | 40 | 40 |
| K-0902 | Meet requirements for the installation and maintenance of medical gas and medical vacuum systems. Gas, Vacuum, and Electrical Systems Deficiencies | 34 | 32 |
| K-0909 | Ensure gas and vacuum piping is labeled. Gas, Vacuum, and Electrical Systems Deficiencies | 30 | 28 |
| K-0231 | Provide large enough exits. Egress Deficiencies | 29 | 29 |
| K-0251 | Conform to length requirements for dead end corridors. Egress Deficiencies | 28 | 26 |
| K-0379 | Have proper openings in smoke barrier doors. Smoke Deficiencies | 28 | 28 |
| F-0907 | Provide enough space and equipment to meet each resident's needs Environmental Deficiencies | 20 | 20 |
| K-0255 | Ensure that suites are correctly sub-divided by noncombustible or limited-combustible construction. Egress Deficiencies | 20 | 20 |
| F-0910 | Ensure resident rooms meet each resident's needs. Environmental Deficiencies | 19 | 19 |
| K-0525 | Enure that solid fuel-burning fireplaces are not in patient sleeping areas. Services Deficiencies | 19 | 18 |
| K-0524 | Ensure that gas fire places are out of the reach of patients and can be shut off if unit is working improperly. Services Deficiencies | 18 | 17 |
| K-0532 | Have a properly installed and maintained dumbwaiter or escalator. Services Deficiencies | 17 | 16 |
| K-0254 | Provide hallway or ground-level exits in all residents' rooms. Egress Deficiencies | 16 | 12 |
| K-0400 | Meet fire sprinkler requirement for tall buildings. Miscellaneous Deficiencies | 16 | 16 |
| K-0523 | Ensure that HVAC heat units are suspended and out of the reach of patients and can be shut off if unit is working improperly. Services Deficiencies | 16 | 16 |
| K-0906 | Ensure gas cylinders are properly stored. Gas, Vacuum, and Electrical Systems Deficiencies | 16 | 16 |
| K-0904 | Have a properly installed medical gas master alarm panel. Gas, Vacuum, and Electrical Systems Deficiencies | 14 | 14 |
| K-0373 | Have enough space near smoke barriers to protect residents. Smoke Deficiencies | 13 | 12 |
| K-0261 | Have properly spaced exits within rooms. Egress Deficiencies | 12 | 9 |
| F-0906 | Provide enough power supply for lighting all entrances and exits; equipment for fire detection and alarm systems, and extinguishers. Environmental Deficiencies | 11 | 11 |
| K-0905 | Ensure that gas containers are correctly designed and tested, and in locations that are labeled. Gas, Vacuum, and Electrical Systems Deficiencies | 11 | 11 |
| K-0924 | Ensure that anesthesia apparatus are tested after any adjustment, modification or repair. Gas, Vacuum, and Electrical Systems Deficiencies | 11 | 11 |
| F-0916 | Ensure each resident has a room at or above ground level. Environmental Deficiencies | 10 | 4 |
| F-0918 | Provide a bathroom in or located near each resident’s room. Environmental Deficiencies | 10 | 10 |
| K-0162 | Have a combustible roofing system that meets safety standards. Construction Deficiencies | 10 | 10 |
| K-0253 | Provide two separate exits in rooms of more than 1000 square feet. Egress Deficiencies | 6 | 5 |
| F-0441 | Have a program that investigates, controls and keeps infection from spreading. Environmental Deficiencies | 5 | 5 |
| F-0915 | Ensure each resident room has a window to the outside that meets requirements Environmental Deficiencies | 5 | 5 |
| K-0381 | Provide outside doors or windows in every resident room. Smoke Deficiencies | 4 | 4 |
| F-0913 | Provide bedrooms that have direct access to an exit hallway. Environmental Deficiencies | 3 | 2 |
| K-0112 | Add automatic sprinklers after major renovation. Construction Deficiencies | 3 | 3 |
| F-0323 | Ensure that a nursing home area is free from accident hazards and provide adequate supervision to prevent avoidable accidents. Environmental Deficiencies | 2 | 2 |
| K-0752 | Ensure new upholstered furniture and mattresses meet char length and heat release criteria. Miscellaneous Deficiencies | 2 | 2 |
| K-0910 | Ensure when modifications are made that breach pipelines, testing is conducted on downstream portions of the piping system. Gas, Vacuum, and Electrical Systems Deficiencies | 2 | 2 |
| F-0372 | Dispose of garbage and refuse properly. Environmental Deficiencies | 1 | 1 |
| F-0465 | Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public. Environmental Deficiencies | 1 | 1 |
| F-0469 | Make sure there is a pest control program to prevent/deal with mice, insects, or other pests. Environmental Deficiencies | 1 | 1 |
| K-0025 | Walls that prevent smoke from passing through and would resist fire for at least one hour. Smoke Deficiencies | 1 | 1 |
| K-0038 | Exits that are accessible at all times. Egress Deficiencies | 1 | 1 |
| K-0072 | Exits that are free from obstructions and can be used at all times. Interior Deficiencies | 1 | 1 |
| K-0130 | Have other fire safety features required by fire safety codes. Miscellaneous Deficiencies | 1 | 1 |
| K-0322 | Ensure that laboratories employing quantities of flammable, combustible, or hazardous materials have fire resistant walls and automatic sprinkler system. Smoke Deficiencies | 1 | 1 |
| K-0933 | Ensure that periodic evaluations are made of hazards that could be encountered during surgical procedures, and fire prevention procedures are established. Smoke Deficiencies | 1 | 1 |
| F-0252 | Provide a safe, clean, comfortable and home-like environment; and allow residents to use personal belongings to the extent possible. Environmental Deficiencies | 0 | 0 |
| F-0253 | Provide housekeeping and maintenance services. Environmental Deficiencies | 0 | 0 |
| F-0254 | Provide clean bed and bath linens that are in good condition. Environmental Deficiencies | 0 | 0 |
| F-0256 | Provide adequate and comfortable lighting levels in all areas. Environmental Deficiencies | 0 | 0 |
| F-0257 | Maintain comfortable and safe temperature levels. Environmental Deficiencies | 0 | 0 |
| F-0258 | Maintain comfortable sound levels. Environmental Deficiencies | 0 | 0 |
| F-0454 | Be designed, built, equipped, or well kept to protect the health and safety of residents, workers, and the public. Environmental Deficiencies | 0 | 0 |
| F-0455 | Provide enough power supply for lighting all entrances and exits; equipment for fire detection and alarm systems, and extinguishers. Environmental Deficiencies | 0 | 0 |
| F-0456 | Keep all essential equipment working safely. Environmental Deficiencies | 0 | 0 |
| F-0457 | Provide bedrooms that hold no more than 4 residents per room. Environmental Deficiencies | 0 | 0 |
| F-0458 | Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms. Environmental Deficiencies | 0 | 0 |
| F-0459 | Provide bedrooms that have direct access to an exit hallway. Environmental Deficiencies | 0 | 0 |
| F-0460 | Provide bedrooms that don't allow residents to see each other when privacy is needed. Environmental Deficiencies | 0 | 0 |
| F-0461 | Make sure each resident has 1) at least one window to the outside in a room; 2) a room at or above ground level; 3) adequate bedding; 4) furniture that meets the resident's needs; or 5) adequate closet space. Environmental Deficiencies | 0 | 0 |
| F-0462 | Provide a bathroom in or located near each resident’s room. Environmental Deficiencies | 0 | 0 |
| F-0463 | Make sure that a working call system is available in each resident's room or bathroom and bathing area. Environmental Deficiencies | 0 | 0 |
| F-0464 | Provide at least one room set aside to use as a resident dining room and for activities, that is a good size, with good lighting, air flow and furniture. Environmental Deficiencies | 0 | 0 |
| F-0466 | Have enough backup water supply for essential areas of the nursing home. Environmental Deficiencies | 0 | 0 |
| F-0467 | Have enough outside ventilation via a window or mechanical ventilation, or both. Environmental Deficiencies | 0 | 0 |
| F-0468 | Put firmly secured handrails on each side of hallways. Environmental Deficiencies | 0 | 0 |
| K-0011 | A two-hour-resistant firewall separation. Construction Deficiencies | 0 | 0 |
| K-0012 | Approved construction type or materials. Construction Deficiencies | 0 | 0 |
| K-0014 | Fire resistant interior walls. Interior Deficiencies | 0 | 0 |
| K-0015 | Fire resistant room wall surfaces. Interior Deficiencies | 0 | 0 |
| K-0016 | Fire resistant floor finishes. Interior Deficiencies | 0 | 0 |
| K-0017 | Corridors that are separated from use areas by walls constructed to limit the passage of smoke. Corridor Walls and Doors Deficiencies | 0 | 0 |
| K-0018 | Corridor and hallway doors that block smoke. Corridor Walls and Doors Deficiencies | 0 | 0 |
| K-0019 | Properly constructed windows in hallway walls or doors. Corridor Walls and Doors Deficiencies | 0 | 0 |
| K-0020 | Proper stairway enclosures and vertical shafts. Construction Deficiencies | 0 | 0 |
| K-0021 | Exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. Construction Deficiencies | 0 | 0 |
| K-0022 | Signs that state that exit doors are to be kept closed. Corridor Walls and Doors Deficiencies | 0 | 0 |
| K-0023 | At least two compartments on every floor to protect residents from smoke. Smoke Deficiencies | 0 | 0 |
| K-0024 | Properly sized and located compartments to protect residents from smoke. Smoke Deficiencies | 0 | 0 |
| K-0026 | Enough space near smoke barriers to protect residents. Smoke Deficiencies | 0 | 0 |
| K-0027 | Smoke barrier doors that can resist smoke for at least 20 minutes. Smoke Deficiencies | 0 | 0 |
| K-0028 | Doors of sufficient width and proper construction in smoke barriers. Smoke Deficiencies | 0 | 0 |
| K-0029 | Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishing system. Hazardous Area Deficiencies | 0 | 0 |
| K-0030 | Gift shops separated and protected as hazardous areas. Hazardous Area Deficiencies | 0 | 0 |
| K-0031 | A properly protected laboratory for handling hazardous materials. Laboratories Deficiencies | 0 | 0 |
| K-0032 | At least two remote exits on each floor or fire section of the building. Egress Deficiencies | 0 | 0 |
| K-0033 | Protected exits that allow the resident to escape the building. Construction Deficiencies | 0 | 0 |
| K-0034 | Exit stairways and towers that are smoke proof. Egress Deficiencies | 0 | 0 |
| K-0035 | Large enough exits. Egress Deficiencies | 0 | 0 |
| K-0036 | Properly spaced exits within rooms. Egress Deficiencies | 0 | 0 |
| K-0037 | Dead end corridors. Egress Deficiencies | 0 | 0 |
| K-0039 | Corridors or aisles that are unobstructed and are at least 8 feet in width. Egress Deficiencies | 0 | 0 |
| K-0040 | Resident room doors of proper design and width. Egress Deficiencies | 0 | 0 |
| K-0041 | Hallway or ground-level exits in all residents' rooms. Egress Deficiencies | 0 | 0 |
| K-0042 | Two separate exits in rooms of more than 1000 square feet. Egress Deficiencies | 0 | 0 |
| K-0043 | Rooms that can be unlocked from inside without a key. Egress Deficiencies | 0 | 0 |
| K-0044 | Horizontal exits. Egress Deficiencies | 0 | 0 |
| K-0045 | Proper backup exit lighting. Illumination and Emergency Power Deficiencies | 0 | 0 |
| K-0046 | Emergency lighting that can last at least 1 1/2 hours. Illumination and Emergency Power Deficiencies | 0 | 0 |
| K-0047 | Properly located and lighted "Exit" signs. Illumination and Emergency Power Deficiencies | 0 | 0 |
| K-0051 | A fire alarm system that can be heard throughout the facility. Fire Alarm Systems Deficiencies | 0 | 0 |
| K-0052 | An approved installation, maintenance and testing program for fire alarm systems. Fire Alarm Systems Deficiencies | 0 | 0 |
| K-0053 | An automatic smoke detection system in all hallways. Fire Alarm Systems Deficiencies | 0 | 0 |
| K-0054 | Properly maintained smoke detectors. Fire Alarm Systems Deficiencies | 0 | 0 |
| K-0055 | Outside doors or windows in every resident room. Fire Alarm Systems Deficiencies | 0 | 0 |
| K-0056 | An approved automatic sprinkler system connected to the fire alarm system. Automatic Sprinkler Systems Deficiencies | 0 | 0 |
| K-0059 | A properly installed device for maintaining water pressure in the sprinkler system. Automatic Sprinkler Systems Deficiencies | 0 | 0 |
| K-0060 | A complete sprinkler system with alarm system connection. Automatic Sprinkler Systems Deficiencies | 0 | 0 |
| K-0061 | Properly working alarms on sprinkler valves. Automatic Sprinkler Systems Deficiencies | 0 | 0 |
| K-0062 | Automatic sprinkler systems that have been maintained in working order. Automatic Sprinkler Systems Deficiencies | 0 | 0 |
| K-0063 | An adequate water supply for the sprinkler system. Automatic Sprinkler Systems Deficiencies | 0 | 0 |
| K-0064 | Portable fire extinguishers. Automatic Sprinkler Systems Deficiencies | 0 | 0 |
| K-0066 | Posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. Smoking Regulations Deficiencies | 0 | 0 |
| K-0067 | Heating and ventilation systems that have been properly installed according to the manufacturer's instructions. Services Deficiencies | 0 | 0 |
| K-0068 | An externally vented heating system. Services Deficiencies | 0 | 0 |
| K-0069 | Properly protected cooking facilities. Services Deficiencies | 0 | 0 |
| K-0070 | Restrictions on the use of portable space heaters. Services Deficiencies | 0 | 0 |
| K-0071 | Properly constructed linen or trash chutes. Services Deficiencies | 0 | 0 |
| K-0073 | Restrictions on the use of highly flammable decorations. Interior Deficiencies | 0 | 0 |
| K-0074 | Restrictions on the use of flammable curtains. Interior Deficiencies | 0 | 0 |
| K-0075 | Properly sized and located linen or trash receptacles. Interior Deficiencies | 0 | 0 |
| K-0076 | Proper medical gas storage and administration areas. Medical Gases and Anesthetizing Areas Deficiencies | 0 | 0 |
| K-0077 | Properly constructed piped-in oxygen systems. Medical Gases and Anesthetizing Areas Deficiencies | 0 | 0 |
| K-0078 | Properly constructed and protected anesthetizing areas. Medical Gases and Anesthetizing Areas Deficiencies | 0 | 0 |
| K-0103 | Noncombustible or limited-combustible interior walls. Construction Deficiencies | 0 | 0 |
| K-0104 | Proper construction of ducts through walls designed to prevent smoke passage. Smoke Deficiencies | 0 | 0 |
| K-0105 | Proper lighting for emergency exits. Illumination and Emergency Power Deficiencies | 0 | 0 |
| K-0106 | Proper power supply for life support equipment. Electrical Deficiencies | 0 | 0 |
| K-0107 | An alternate power supply for its alarm system. Illumination and Emergency Power Deficiencies | 0 | 0 |
| K-0108 | Emergency power for alarms and communications systems (new only). Illumination and Emergency Power Deficiencies | 0 | 0 |
| K-0109 | A properly located automatic smoke detector system in all hallways (new only). Fire Alarm Systems Deficiencies | 0 | 0 |
| K-0134 | Emergency showers. Laboratories Deficiencies | 0 | 0 |
| K-0135 | Proper facilities for the use and storage of combustible liquids. Laboratories Deficiencies | 0 | 0 |
| K-0136 | Proper procedures for handling laboratory emergencies. Laboratories Deficiencies | 0 | 0 |
| K-0140 | A properly installed medical gas master alarm panel. Medical Gases and Anesthetizing Areas Deficiencies | 0 | 0 |
| K-0141 | No-smoking signs where oxygen is used. Medical Gases and Anesthetizing Areas Deficiencies | 0 | 0 |
| K-0142 | A properly constructed or installed hyperbaric treatment facility. Medical Gases and Anesthetizing Areas Deficiencies | 0 | 0 |
| K-0143 | Have proper fire barriers, ventilation and signs for the transfilling of oxygen. Medical Gases and Anesthetizing Areas Deficiencies | 0 | 0 |
| K-0144 | Weekly inspections and monthly testing of generators. Electrical Deficiencies | 0 | 0 |
| K-0145 | The appropriate emergency electrical system. Electrical Deficiencies | 0 | 0 |
| K-0146 | A separate and independent backup electrical power source. Electrical Deficiencies | 0 | 0 |
| K-0147 | Properly installed electrical wiring and equipment. Electrical Deficiencies | 0 | 0 |
| K-0153 | Procedures for handling laboratory emergencies. Laboratories Deficiencies | 0 | 0 |
| K-0154 | Back-up procedures in place for a faulty automatic sprinkler system. Automatic Sprinkler Systems Deficiencies | 0 | 0 |
| K-0155 | An approved back-up procedure for a faulty fire alarm system. Fire Alarm Systems Deficiencies | 0 | 0 |
| K-0160 | An elevator that firefighters can control in the event of a fire. Services Deficiencies | 0 | 0 |
| K-0168 | Be of proper construction type and height - slow evacuation Construction Deficiencies | 0 | 0 |
| K-0169 | Be of proper construction type and height - impractical evacuation Construction Deficiencies | 0 | 0 |
| K-0228 | Have properly designed and constructed stairways and smokeproof enclosures. Egress Deficiencies | 0 | 0 |
| K-0256 | Ensure that sleeping suites have required exit access and constant staff supervision. Egress Deficiencies | 0 | 0 |
| K-0257 | Ensure that non-sleeping suites have required exit access. Egress Deficiencies | 0 | 0 |
| K-0258 | Provide enough exits Egress Deficiencies | 0 | 0 |
| K-0259 | Provide enough exits Egress Deficiencies | 0 | 0 |
| K-0292 | Ensure that buildings with life support systems have proper emergency lighting for equipment, exits, and directional signs. Egress Deficiencies | 0 | 0 |
| K-0299 | Provide appropriate exit signage Egress Deficiencies | 0 | 0 |
| K-0323 | Provide properly constructed and protected anesthetizing areas. Smoke Deficiencies | 0 | 0 |
| K-0329 | Have proper enclosures for hazardous areas Smoke Deficiencies | 0 | 0 |
| K-0332 | Ensure that floor finishes have correct flame spread rating. Smoke Deficiencies | 0 | 0 |
| K-0338 | Have proper interior wall and ceiling finish Smoke Deficiencies | 0 | 0 |
| K-0421 | Ensure that building is protected throughout by an automatic sprinkler system. Miscellaneous Deficiencies | 0 | 0 |
| K-0903 | Ensure medical gas and air supply systems in which failure is likely to cause major injury or death, are correctly designated. Gas, Vacuum, and Electrical Systems Deficiencies | 0 | 0 |
| K-0931 | Have a properly constructed or installed hyperbaric treatment facility. Medical Gases and Anesthetizing Areas Deficiencies | 0 | 0 |
| K-8131 | Have proper procedures for controlling chemical spills. Laboratories Deficiencies | 0 | 0 |
| K-8132 | Have a proper laboratory safety education program. Laboratories Deficiencies | 0 | 0 |
| K-8133 | Have properly installed fume hoods. Laboratories Deficiencies | 0 | 0 |
| K-8161 | Have a properly installed and maintained dumbwaiter or escalator. Services Deficiencies | 0 | 0 |
| K-8162 | Have elevators that met current safety standards. Services Deficiencies | 0 | 0 |
| K-8211 | Provide properly installed hallway dispensers for alcohol-based hand rub. Hazardous Area Deficiencies | 0 | 0 |
| K-9131 | Meet requirements for sections of health care facilities separated by fire resistive construction. Construction Deficiencies | 0 | 0 |
| K-9132 | Meet requirements for outpatient facilities located next to inpatient facilities separated by fire resistive construction. Construction Deficiencies | 0 | 0 |
| K-9133 | Install a two-hour-resistant firewall separation. Construction Deficiencies | 0 | 0 |
| K-9161 | Use approved construction type or materials. Construction Deficiencies | 0 | 0 |
| K-9162 | Have a combustible roofing system that meets safety standards. Construction Deficiencies | 0 | 0 |
| K-9211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. Egress Deficiencies | 0 | 0 |